30as Unit1/3.5 48 Cores OPGW Cable For Communication and Overhead Ground Wire

Fiber optic composite overhead ground wire (OPGW) is a type of overhead ground wire containing optical fibers, which has multiple functions such as overhead ground wire and optical communication. It is mainly used for communication lines in 110kV, 220kV, 500kV, 750kV, and new overhead high-voltage transmission systems. OPGW cable can also be used to replace the existing ground wire of old overhead high-voltage transmission systems, add optical communication lines, conduct short-circuit currents, and provide lightning protection. Special structures can be customized according to user needs.

Product Application

  • Communication lines in high-voltage transmission systems;
  • OPGW cable supports two-way communication. It also has functions such as real-time data exchange and smart meter reading.

Product features

1. The cable diameter is relatively large, and a large number of fiber cores can be designed;
2. Stable structure and high reliability;
3. The tensile strength and short-circuit current capacity are relatively large, which can achieve the best balance between mechanical and electrical performance;
4. The best twisted design can obtain the excess length of secondary optical fibers;
5. The number of twisted wire layers can be designed as two or three layers;
6. Single wire can be a combination of aluminum clad steel wire and/or aluminum alloy wire and aluminum wire;

Technology Paramater of 48 Cores OPGW

Item Testing Method Acceptance criteria
Pull GB/T7424.2-E1
Load: Based on changes in fiber optic cable structure
Sample length: not less than 10m;
Link not less than 100m
Duration: 1 minute
40% RTS fiber has no significant strain (0.01%), and the fiber has no significant additional attenuation (0.03dB).
60% RTS fiber strain ≤ 0.25%, fiber additional attenuation ≤ 0.05dB (after tension cancellation, there is no significant residual additional attenuation of the fiber (0.03dB)
Flattening GB/T7424.2-E3
Load: According to the above table,
Test 3 points for a duration of 10 minutes
After the experiment, the additional attenuation of single-mode fiber at 1550nm wavelength should not exceed 0.05dB/fiber, and there should be no mechanical damage to the OPGW.
Seepage water GB/T7424.2-F5
Time: 1 hour
Sample length: 0.5m Water height: 1m
No water seepage
Temperature cycling GB/T7424.2-F1
Sample length: not less than 500m
Temperature range: -40 ºC~+70 ºC
Number of cycles: 2
Insulation time: not less than 12 hours
After experiment,the additional attenuation of single-mode fiber at 1550nm wavelength should not exceed 0.1dB.